Gossen Metrawatt R6000 8-Channel Controller in Top-Hat Rail Housing
Temperature controller for machines and systems with central control and display concepts. Connection to central controls via various fieldbus interfaces or integrated service interface.
- PDPI - Algorithm for Induction Heating Systems - see special items below
- pH-Value Control - see special items below
- Virtual analog outputs
- Ratio control
- Billing of several measuring inputs to determine the controlled variable
- Cycle time: 10 ms per channel
- Overshoot-free PDPI controller, limit transducer, cyclic duration controller
- Freely configurable control channels
- Control parameter adaption can be started at any time
- 2-step, 3-step controller, continuous action, step-action and split-range controller
- Fixed value, cascade, differential and switch controller
- Data logger, 3600 sampling values each from setpoint and actual value for 8 channels
- Alarm history records up to 100 error states with timestamp
- Cost Reduction for Energy via Intelligent Power Limitation -> more
- Hot-runner control with actuating circuit and booster circuit
- Water cooling control (non-linear cooling effect with evaporation)
- Actual value management by groups for the avoidance of thermal stressing
- Remote cold junction - only with original cold junction Z306A possible
- 2nd set of parameters
- Setpoint ramp
- Feed-forward control for the avoidance of undershooting and overshooting
- Control zones can be assigned to groups
- All zones can be deactivated as desired with internal or external signal
- Absolute or relative limit value monitoring, start-up inhibiting, normally open / normally closed contact
- 8 sensor inputs, thermocouples or Pt100, individually selectable with software
- Monitoring for sensor breakage, cable interruption, polarity reversal and short-circuiting
- Regulated temperature becomes active in the event of sensor breakage
- Resistant to interference caused by leakage current at thermocouples
- 16 binary inputs / outputs with short-circuit detection and self-restoring overload protection
- Heating circuit monitoring without additional transformer
- Voltage compensated heating current monitoring with external standard transformer
- Remote diagnosis with numerous monitoring functions
- Mapping - checks sensor-heater assignment
- RS 232 service interface for configuration and data exchange with free software
- 24 V DC power supply