Kyoritsu KEW 6016 Multi Function Testers
Continuity Measurement
Continuous testing can be carried out by use of the test button lockdown feature. A selectable buzzer gives instantaneous indication of continuity. Null facility eliminates the test lead resistance from the results, the nulled value is retained even if the instrument is switched off. Live circuit warnings are given by a flashing LED, buzzer and indication on the display.
Insulation Measurement
Three selectable test voltages 250V, 500V and 1000V. An auto-discharge function ensures that circuits are not hazardous after testing. A red LED gives warning of high voltage output during testing and discharging of the circuit. In case of connecting to a live circuit, a live circuit warning is given by flashing LED, buzzer and indication on the display.
Loop Impedance Measurement
A patented (ATT) low current loop impedance test enables high accuracy loop measurements and quick testing without tripping RCD's.
A high current alternative is selectable for even higher accuracy and instantaneous results. The subsequent test will default to the low current test, this saves any inadvertent tripping of the RCD. The KEW 6016 allows also for phase to phase loop tests.
| Continuity | ||||||||
|---|---|---|---|---|---|---|---|---|
| Insulation Resistance | ||||||||
| Loop Impedance | ||||||||
| PSC (L-N / L-L) / PFC (L-PE) | ||||||||
| RCD | ||||||||
| RCD (Uc) | ||||||||
| Earth | ||||||||
| Phase Rotation | ||||||||
| Volts | ||||||||
| Range | 20/200/2000(Auto-ranging) | |||||||
| Open circuit voltage (DC) | 5V0% (*1) | |||||||
| Short circuit current | Greater than 200mA | |||||||
| Accuracy | .1(0 - 0.19 %rdg+8dgt (0.2 - 2000 | |||||||
| Range | 20/200Mbr />(Auto-ranging) | 20/200/2000M(Auto-ranging) | ||||||
| Open circuit voltage (DC) | 250V+25% -0% | 500V+25% -0% | 1000V+20% -0% | |||||
| Rated current | 1mA or greater @ 250k/td> | 1mA or greater @ 500k/td> | 1mA or greater @ 1M/td> | |||||
| Accuracy | %rdg+6dgt (0 - 19.99M %rdg+6dgt (20 - 200M | %rdg+6dgt (0 - 199.9M %rdg+6dgt (200 - 2000M | ||||||
| Function | L-PE | L-PE (ATT) | L-N / L-L | |||||
| Rated Voltage | 100 - 260V 50/60Hz | L-N: 100 - 300V L-L: 300 - 500V 50/60Hz | ||||||
| Nominal Test Current at 0br />External Loop: Magnitude/ Duration (*2) | 20 6A/20ms 200 2A/20ms 2000 15mA/500ms | L-N: 6A/60ms N-PE: 10mA/approx. 5s | 20 6A/20ms | |||||
| Range | 20/200/2000br />(Auto-ranging) | 20/200/2000br />(Auto-ranging) (L-N < 20 | 20/td> | |||||
| Accuracy | %rdg+4dgt(*3) %rdg+8dgt(*4) | %rdg+6dgt (*3) %rdg+8dgt(*4) | %rdg+4dgt (*3) %rdg+8dgt(*4) | |||||
| Function | PSC | PFC | PFC (ATT) | |||||
| Rated Voltage | 100 - 500V 50/60Hz | 100 - 260V 50/60Hz | ||||||
| Nominal Test Current at 0br />External Loop: Magnitude/ Duration (*5) | 6A/20ms | 6A/20ms 2A/20ms 15mA/500ms | L-N: 6A/60ms N-PE: 10mA/approx. 5s | |||||
| Range | 2000A/20kA Auto-Ranging | |||||||
| Accuracy | PSC / PFC accuracy is derived from measured loop impedance specification and measured voltage specification | |||||||
| Function | X1/2 | X1 | X5 | Ramp | Auto | |||
| Trip current setting | 10/30/100/300/ 500/1000mA | 10/30/ 100mA | 10/30/ 100/300/ 500mA | Depending on the accuracy at each function. Measurement sequence: X1/2 01/2 180br />1 01 180br />5 05 180br />Measurements with x5 are not carried out for RCDs with nominal current of 100mA or more. | ||||
| Trip current Duration | 2000ms | G: 550ms S: 1000ms | 410ms | Goes up by 10% from 20% to 110% G:300ms/ S:500ms X10 times | ||||
| RatedVoltage | 230V+10%-15% 50/60Hz | |||||||
| Accuracy | AC Type: -8% - -2% A Type: -10% - 0% | AC Type: +2% - +8% A Type: 0% - +10% | AC Type: % A Type: 0% | |||||
| Trip time: %rdg+3dgt | ||||||||
| Function | UC | |||||||
| Rated Voltage | 230V+10% - 15% 50/60Hz | |||||||
| Range | 100.0V | |||||||
| Test current | 1/2In (max150mA) | |||||||
| Accuracy | +5% - +15%rdg, dgt | |||||||
| Range | 20/200/2000Auto-Ranging | |||||||
| Accuracy | 20 %rdg+0.1br />200/2000 %rdg+3dgt (Auxiliary earth resistance 100%) | |||||||
| Rated Voltage | 50-500V 50/60Hz | |||||||
| Remarks | Correct phase sequence: are displayed "1.2.3" and Reversed phase sequence: are displayed "3.2.1" and | |||||||
| Function | Volts | Frequency | ||||||
| Rated Voltage | 25 - 500V, 45 - 65Hz | |||||||
| Measuring range | 25 - 500V | 45 - 65Hz | ||||||
| Accuracy | %rdg+4dgt | .5%rdg+2dgt | ||||||
| Applicable standards | IEC 61010-1 CAT III 300V (500V L to L) Pollution degree 2, IEC 61010-031, IEC 61557-1, 2, 3, 4, 5, 6, 7, 10, IEC 60529 (IP40), IEC 61326 (EMC) |
|---|---|
| Power source | LR6 X 8 |
| Dimensions | 136(L) X 235(W) X 114(D)mm |
| Weight | 1350g (including batteries.) |
| Included Accessories | 7188A (Distribution board fuse test lead set) 7196A (Test leads with remote control switch) 7218A (Power cord [EU]) (*6) 7228A (Earth resistance test leads) 8032 (Auxiliary earth spikes) 8212-USB (USB adaptor with KEW Report (Software)) 9142 (Carrying case) 9121 (Shoulder strap) Cord case, Buckle, Battery, Instruction manual |
| Optional Accessories | 8212-RS232C (RS232C adaptor with KEW Report (Software)) |
(*1): Voltages are output when measurement resistance is under 2100 ohm.
(*2): at 230V
(*3): 230V+10%-15%
(*4): voltages except for (*3)
(*5): at 230V
(*6): 7187A (Power cord [UK]), 7221A (Power cord [SA]), 7222A (Power cord [AU])