Page 930 - techequipmentscatalogue2016
P. 930
TERTEST

.---_._,- •ii i C300 Power Calibrator and Tester
i
..-.... ..-.,... ..-n..• C300 j ISO 9001 :2008
Th ree Phase Power Cahbfator & TeslCf i
o Voltage source up to 500 V
•••••••• • o 3- phase current source up to 120A and

1- phase up to 360A

o Voltage and current harmonics

programming up to 31
o Power quality parameters simulation

o Impulse input for electricity meters testing

o Start/ stop inputs for protective relay testing
o AC measurement input for transformers

and clamps testing
o DC measurement input for transducer

testing
o RS 232C interface and personal computer

software Calpro 300

PARAMETERS OF THE C 300 CALIBRATOR

Parameter Range Setting range Resolution Accuracy Maximum Load

60V 0,SOOO...60,0000V 0,000 ] V 460mA @60V

Voltage U 130V 1,000 ...130,000V O,OOlV ±0,04% of setting 230mA @ 130V
2S0V 2,000 ...2S0,000V 0,00 1V ±O,OI% ofrange 11SmA@2S0V

SOOV S,OOO ...SOO,OOOV 0,001 V SSmA@SOOV

Current I O,SA O,OOSOOO ...O,SOOOOOA O,OOOOOlA ±0,04% of setting lSV@O,SA
6A 0,OSOOO .. .6,00000A O,OOOOIA ±0,01% of range
20A 0 ,2000 ... 20 ,0000A O,OOOlA 7V@6A
±O, ]% of setting
120A 1,000 ... 120,000A 0,001 A ±O,OI% of range 2,2V@20A

0,6V@ 100A
0,5V @ 120A

Frequency f 40 ,000 .. .99,999Hz O,OOlHz ±0,002Hz
±0,01 Hz
Phase shift q> 100,000 .. .SOO,000Hz O,OO IHz ±O,l o *)
Active Power ±O,OS% 'l,**)
Reactive Power 0,00 ...±360 ,00 ° 0,01 ° ±O,OS% '):')
Apparent Power ±O,OS%
0... 3xSOOOO,OW O,OOOOI - IW ±O,O I% ±O,OO Is
Time ±O,OS% 'J:*)
Energy 0.. .3xSOOOO,Ovar O,OOOOI-lvar

0... 3xSOOOO,OV A O,OOOO I-IVA

1.. .36000s Is

calc. from settings and reso lution of power and time

Harmo nics amplitude and phase of harmonics in range 0... 100% and 0...360° up to 31 of hannonics or 3200Hz

*) from 10% of current range and 30% of voltage range, in frequency band 45-65Hz
**) power P (Q) error far casq> (sinq» = 1

924 www.tech-equipments.comlsales@tech-equipments.com